beautypg.com

Certifications 75, Environmental conditions 75, Safety test 75 – West Control Solutions Pro-4 User Manual

Page 75: Technical data

background image

cUL certification

(Type 4x, indoor use)

For compliance with cUL certificate,the follow-

ing information must be taken into account:

w

Use only 60 / 75 or 75°C copper (Cu) wire.

w

Tighten the terminal- screws with a torque

of 0,5 - 0,6 Nm

Ambient temperature: ≤ 40°C

Power supply: ≤ 250 V AC

Electrical connections

w

flat-pin terminals 1 x 6,3mm or 2 x 2,8mm to

DIN 46 244 or

w

screw terminals for 0,5 to 2,5mm²

On instruments with screw terminals, the

insulation must be stripped by min. 12 mm.

Choose end crimps accordingly.

Mounting

Panel mounting with two fixing clamps at top/ bot-

tom or right/left, high-density mounting possible

Mounting position:

uncritical

Weight:

0,27kg

Accessories delivered with the unit

Operating manual

Fixing clamps

Technical data

KS 90-1 / KS 92-1

75