Configuration level

Configuration parameters

34

KS 90-1 / KS 92-1

Name Value range Description

Default

2

thermocouple type K (-100...1350°C), NiCr-Ni

3

thermocouple type N (-100...1300°C), Nicrosil-Nisil

4

thermocouple type S (0...1760°C), PtRh-Pt10%

5

thermocouple type R (0...1760°C), PtRh-Pt13%

6

thermocouple type T (-200...400°C), Cu-CuNi

7

thermocouple type C (0...2315°C), W5%Re-W26%Re

8

thermocouple type D (0...2315°C), W3%Re-W25%Re

9

thermocouple type E (-100...1000°C), NiCr-CuNi

10

thermocouple type B (0/100...1820°C), PtRh-Pt6%

18

special thermocouple

20

Pt100 (-200.0 ... 100,0 °C)

( -200,0 ... 150,0°C with reduced lead resistance: measuring

resistance + lead resistance ß160 [ )

21

Pt100 (-200.0 ... 850,0 °C)

22

Pt1000 (-200.0 ... 850.0 °C)

23

special 0...4500 Ohm (preset to KTY11-6)

24

special 0...450 Ohm

30

0...20mA / 4...20mA 1

41

special -2,5...115 mV 1

42

special -25...115 0mV 1

50

potentiometer 0...160 Ohm 1

51

potentiometer 0...450 Ohm 1

52

potentiometer 0...1600 Ohm 1

53

potentiometer 0...4500 Ohm 1

Corr

Measured value correction / scaling

0

0

Without scaling

1

Offset correction (at CAL level)

(offset entry is at controller CALlevel)

2

2-point correction (at CAL level)

(calibration is at controller CALlevel)

3

Scaling (at PArA level)

4

Automatic calibration (DAC)

In.F

-1999...9999

Alternative value for error at INP3

If a value is adjusted, this value is used for display and calculation

in case of error (e.g. FAIL).

a Before activating a substitute value, the effect in the

control loop should be considered!

OFF

fAI3

Forcing INP3 (only visible with BlueControl!)

0

0

No forcing

1

Forcing via serial interface

1 with current and voltage input signals, scaling is required (see chapter 5.3)