Configuration parameters
Lim
Name Value range Description
Default
Fnc.1
Fnc.2
Fnc.3
Function of limit 1/2/3
1
0
switched off
1
measured value monitoring
2
Measured value monitoring + alarm latch. A latched limit value
can be reset via error list or via a digital input, or by pressing key
Ò or
è
(-> LOGI/ Err.r)
3
signal change (change/minute)
4
signal change and storage (change/minute)
Src.1
Src.2
Src.3
Source of Limit 1/2/3
1
0
process value
1
control deviation xw (process value - set-point)
2
Control deviation Xw (=relative alarm) with suppression after
start-up and setpoint change
After switch-on or setpoint change, alarm output is suppressed,
until the process value was within the limits once. At the latest after
elapse of time 10 ti1 the alarm is activated. (ti1 = integral
time 1; parameter r Cntr)
ti1 switched off (ti1 = 0) is considered as Î , i.e. the alarm is
not activated, until the process value was within the limits once.
3
measured value INP1
4
measured value INP2
5
measured value INP3
6
effective setpoint Weff
7
correcting variable y (controller output)
8
control variable deviation xw (actual value - internal setpoint) =
deviation alarm to internal setpoint
9
difference x1 - x2 (utilizable e.g. in combination with process value
function “mean value” for recognizing aged thermocouples
11
Control deviation (=relative alarm) with suppression after start-up
and setpoint change without time limit
After switch-on or setpoint change, alarm output is suppressed,
until the process was within the limits once.
HC.AL
Alarm heat current function (INP2)
0
0
switched off
1
Overload short circuit monitoring
2
Break and short circuit monitoring
LP.AL
Monitoring of control loop interruption for heating (see page 68)
0
0
switched off / inactive
1
active. If ti1=0 LOOP alarm is inactive!
dAc.A
DAC alarm function (see page 68)
0
0
DAC alarm switched off / inactive
1
DAC alarm active
Hour
OFF...999999
Operating hours (only visible with BlueControl
!)
OFF
Swit
OFF...999999
Output switching cycles (only visible with BlueControl
!)