Configuration level – West Control Solutions Pro-4 User Manual
Page 42
+
BlueControl - the engineering tool for the BluePort controller series
3 engineering tools with different functionality facilitating the device configu-
ration and parameter setting are available (see chapter 9: Accessory equipment
with ordering information).
In addition to configuration and parameter setting, blue control
is used for
data acquisition and offers long-term storage and print functions. Blue control
is connected to the device via the front-panel interface "BluePort
" by means
of PC (Windows 95 / 98 / NT) and a PC adaptor.
Description BlueControl
: see chapter 8: BlueControl (page 70).
Configuration level
Configuration parameters
42
KS 90-1 / KS 92-1
Name Value range Description
Default
CDis3
Display 3 controller operating level (only visible with BlueControl!)
2
0
No value / only text
1
Display of value
2
Output value as bargraph
3
Control deviation as bargraph
4
Process value as bargraph
TDis3
2...60
Display 3 display alternation time [s] (only visible with BlueControl!)
10
T.dis3
8 Zeichen
Text display 3 (only visible with BlueControl!)
T.InF1
8 Zeichen
Text Inf.1 (only visible with BlueControl!)
T.InF2
8 Zeichen
Text Inf.2 (only visible with BlueControl!)
Lin
(only visible with BlueControl
Name
Value range
Description
Default
Lin
Linearization for inputs INP1 or INP3
Access to this table is always with selection special
thermocouple for InP.1 or InP.3or with setting S.Lin
= 1: special linearization for linearization. Default: KTY
11-6 (0...4,5 kOhm)
U.LinT
Unit of linearization table
0
0
No unit
1
In Celsius [°C]
2
In Fahrenheit [°C]
In.1
-999.0..99999
Input value 1
The signal is in [µV] or in [[] dependent of input type
1036
Ou.1
0,001...9999 Output value 1
Signal assigned to In.1
-49,94
In.2
-999.0..99999 Input value 2
The signal is in [µV] or in [[] dependent of input type
1150
Ou.2
0,001...9999 Output value 2
Signal assigned to In.2
-38,94
:
:
:
:
:
:
:
:
In.16
-999.0..99999 Input value 16
The signal is in [µV] or in [[] dependent of input type
4470
Ou.16
0,001...9999 Output value 1 6
Signal assigned to In.16
150,0