3.6 Manual self-tuning
The optimization aid can be used with units on which the control parameters shall
be set without self-tuning.
For this, the response of process variable x after a step change of correcting varia-
ble y can be used. Frequently, plotting the complete response curve (0 to 100%)
is not possible, because the process must be kept within defined limits. Values T
g
and x
max
(step change from 0 to 100 %) or ∆t and ∆x (partial step response) can
be used to determine the maximum rate of increase v
max
.
y
= correcting variable
Y
h
= control range
Tu
= delay time (s)
Tg
= recovery time (s)
X
max
= maximum process value
V
max
= Xmax
Tg
= {
{
x
t
= max. rate of increase of process value
The control parameters can be determined from the values calculated for delay
time T
u
, maximum rate of increase v
max
, control range X
h
and characteristic K
according to the formulas given below. Increase Xp, if line-out to the set-point
oscillates.
Operation
Manual self-tuning
24
KS 90-1 / KS 92-1
Tu
Tg
t
x
y
100%
0%
t
Yh
Xmax
{X
{t