4.4.4 Heating and cooling with constant period ( CyCl= 3 )
1 and t2 are met in the overall output
range . To prevent unreasonably short
pulses, parameter tp is used for adju-
sting the shortest pulse duration. With
small correcting values which require a
pulse shorter than the value adjusted in
tp, this pulse is suppressed. However,
the controller stores the pulse and totali-
zes further pulses, until a pulse of dura-
tion tp can be output.
Parameters to be adjusted:
t1 : Min. cycle time 1 (heating) [s]
( PArA/ Cntr)
t2 : min. cycle time 2 (cooling) [s]
tp: min. pulse length [s]
Configuration level
Switching behaviuor
46
KS 90-1 / KS 92-1
50%
50%
t1 t2
/
tp
tp
30%
70%
20%
80%
10%
90%
t1 t2
/
See also other documents in the category West Control Solutions Equipment:
- 2300 (18 pages)
- 3300 (2 pages)
- 4100+ (177 pages)
- N4100 (79 pages)
- N4400 (38 pages)
- N6500 (2 pages)
- N6600 (114 pages)
- N8800 (88 pages)
- N8840 (90 pages)
- 9300 (2 pages)
- 9500 (24 pages)
- D280-1 (49 pages)
- KS 40-1 (60 pages)
- KS 40-1 Burner (40 pages)
- KS 45 (76 pages)
- KS 50-1 (72 pages)
- KS 90-1 (84 pages)
- KS 90-1 Programmer manual (84 pages)
- KS 94 (44 pages)
- ProVU 4 (184 pages)
- Pro-16 (88 pages)
- Pro-8 (72 pages)
- ProEC44 (274 pages)
- CI 45 (60 pages)
- SG 45 (56 pages)
- DataVU 5 (136 pages)
- DataVU 7 (208 pages)
- MRC 5000 Controller Manual (32 pages)
- MRC 5000 Recorder Manual (32 pages)
- MRC 7000 Controller Manual (74 pages)
- MRC 7000 Recorder Manual (64 pages)
- MRC 7000 Profiler Manual (84 pages)
- MRC 8000 (76 pages)
- MRC 9000 (318 pages)
- N8080 (for 1xxx) (40 pages)
- N8080 (for 2xxx) (39 pages)
- TB 40-1 Temperature Limiter (32 pages)
- TB 40-1 Temperature Monitor (32 pages)
- TB 45 Temperature Limiter (51 pages)
- TB 45 Temperature Monitor (52 pages)
- CALogix (44 pages)
- KS 800 Operating Instructions (36 pages)
- KS 800 ISO1745 Interface Manual (34 pages)
- KS 800 Profibus Interface Manual (52 pages)