Field troubleshooting 25, A qua m etrix – Metex 3200U Ultrasonic Flow & Level Monitor User Manual
Page 25
FIELD TROUBLESHOOTING
SYMPTOMS
CHECK
Display - full scale
A
- zero
B
- erratic - random
C
- drifting up
D
- drifting down
E
ECHO LOSS
prompt - flashing
F
Calibration Non-Linear
H
SYMPTOMS
FAULTS
SOLUTIONS
Unit “See’s” Wrong Target Due To:
A,C,D,F
- sensor not aimed correctly
A,F,D
- condensation/dust/dirt buildup on
sensor
- Clean carefully (do not scratch sensor face)
A,D
- sensor mounting stand pipe
- Lower Sensor below stand pipe intrusion
- too long / - too narrow
- dirty / - gasket intruding
C,E
- very turbulent flow in open channel
- Increase
RejTime (CALIBRATION
menu)
- install stilling well on flume or weir
C,E
- very turbulent level in tank
- Increase
RejTime (CALIBRATION
menu)
- change tank fill method
Unit Picks-Up Interference Due To:
A,C
- noise from high pressure fill
- Install submerged fill pipe
A,D
- sensor coupling over tightened
- Hand tighten only (like a light bulb)
A,D
- sensor coupling not used
- Use coupling supplied
C
- other ultrasonic unit in close proximity
- Synchronize
Electrical interference:
C
- sensor cable connections reversed
C,G
- through sensor cable
- Use properly grounded metal conduit
C
- sensor cable extended and junction not
insulated
- Use metal Junction Box
C,G
- through enclosure
- Use metal enclosure
C,G
- through 4-20mA output cable
- Use shielded twisted pair (shielded to AC
ground)
- Use grounded metal conduit
C,G
- wiring or installation close to variable
speed drive or inverter
- Follow V.S.D. manufacturer’s instructions
for Drive grounding, wiring and shielding
AquaMetrix
Ultrason
Page 25