Simul

The Output simulation function controls the 4-20mA output, digital display
and control relays. Use it to simplify calibration of remote devices such as
chart recorders or remote displays, and to test Relay set-points. Simulation
digits are shown as a percentage of full scale. Use the

Çand ÈArrow keys to

simulate

0%

(4mA),

100%

(20mA), and increments of .05% (.008mA).

Increments will automatically accelerate when the

Зor И is continuously

pressed.

4mA ADJ

20mA ADJ

Use to fine tune the 4mA and 20mA calibration of the 4-20mA output.
Adjustment range is +1mA to –1mA in 0.002mA steps
Important: The 4-20mA output will be forced to 4mA and 20mA respectively
during these adjustments.

New Password

position cursor under digits and set new number between

00

and

99

.

Com 24 48 96 192

Optional (with Data Logger) Speed of RS-232C transmission. Select

2400

,

4800

,

9600

or

19200

baud rate (must be set to match baud rate in

‘AquaMetrix Logger’ software and any modems used for serial
communication).