Calibration - for open channel flow 11, A qua m etrix, Then è to get to – Metex 3200U Ultrasonic Flow & Level Monitor User Manual
Page 11: Then, Ultrason page 11
CALIBRATION
- for Open Channel Flow
1. Before starting the calibration determine:
a)
MAX RANGE = ____________________
(Maximum range = distance from the Sensor to Zero
level point)
b)
MAX LEVEL
= ____________________
(Maximum level of flow through flume or weir)
c)
MIN RANGE
= __________________
(Distance from sensor to Max Level)
Minimum range = MAX RANGE - MAX LEVEL
(must be at least 8" / 20.3 cm depending on sensor
model).
2. Check the maximum range with the sensor installed by:
a)
Use
Æ to get to
UNITS/MODE
then
È to get to
Range
, then
Store? Yes
(NOTE: flow must be at zero flow)
or
b)
Carefully measure distance from sensor to zero level
with tape measure.
AquaMetrix
Ultrason
Page 11
MinRg
1.333 ft
MaxRg
32.00 ft
4mA @
0.00 %
20mA @
100.00 %
CALIBRATION
Damping
20
%
RejTime
08 s
Store?
Yes
RELAY PARAMETERS
FLUME SELECTION
PALMER BOWLUS
SENSOR
ZERO LEVEL
MAX
RANGE
MIN
RANGE
MAX LEVEL
V-NOTCH
SENSOR
ZERO LEVEL
MAX
RANGE
MAX LEVEL
MIN
RANGE