Calibration - for level 10, A qua m etrix – Metex 3200U Ultrasonic Flow & Level Monitor User Manual

Page 10

background image

CALIBRATION
- for Level/Inventory Applications

1. Before starting the calibration determine:

a)

MAX RANGE = ________________
(Maximum range = distance from Sensor to Zero
level)

b)

MAX LEVEL

= ________________

(Maximum level of product being measured)

c)

MIN RANGE

= ________________

(Distance from sensor to Max Level)
Minimum range = MAX RANGE - MAX LEVEL
(must be at least 8" / 203 mm depending on sensor
model)

2. Check the maximum range with the sensor installed by:

a)

Use

Æ to get to

UNITS/MODE

then

È to get to

Range

, then

Store?

Æ

Yes

(NOTE: liquid must be at zero level)
or

b)

Carefully measure distance from sensor to zero
level with tape measure.

MINIMUM RANGE:

At

CALIBRATION

- Press

È to get to

MinRg

- Press

Æ to move the cursor under the digits

- Use

È or Ç to set the minimum range

Note:

MinRg

must be

³12" (30.5 cm) for US2-1A1A

sensors and

³ 16" (40.6 cm) for US2-2A1B sensors except

in

Hrt

mode. For correct tank volume calculation in

Hrt

mode

MinRg

must be the actual distance from the end of

the sensor to the top of the tank (any value

³0). In

Level

or

Range

modes the Ultrason will only accept

MinRg

values

³ 8" (20.3 cm).

- Press

Æ to return to

MinRg

MAXIMUM RANGE:

Press

È to get to

MaxRg

Repeat as for

MinRg

AquaMetrix

Ultrason

Page 10

MAX LEVEL

ZERO LEVEL

MIN RANGE

TANK INVENTORY
RANGE MODE

SENSOR

0%

100%

MAX RANGE

MAX LEVEL

ZERO LEVEL

MAX
VOLUME

MAX RANGE

MIN RANGE

TANK INVENTORY
LEVEL MODE

SENSOR

100%

0%

TANK INVENTORY
HORIZONTAL ROUND TANK (HRT) MODE

MAX RANGE

MAX

VOLUME

MIN RANGE