Fire-Lite PS Tools MS-9600 User Manual
Page 88
80
636 Pt Addr. Panel
PS-Tools
04/2010
Upload/Download Configuration Data
•
In the Event Codes tab, you can view the information such as values configured to
upload or download, details on central station, event codes description, active value,
and restoral.
2.Under Download to Panel, you can select any of the following configuration data option and then
click Download to Panel.
3.
Click Manual Evacuate to generate a Drill Activated Trouble at fire panel. The Drill Activated
trouble sounds all Silenceable devices and NACs connected to the FACP.
4.
Click Restore Evacuate to clear the Drill Activated trouble and restore the fire panel to Normal
state. The sounding of the Silenceable devices and the NACs continues. Press Signal Silence
button in the fire panel keypad to stop the sounders and NACs.
5.
Click Trouble Silence to silence all the trouble events in the fire alarm system.
6.
Click Clear History to clear all the History data in the fire panel. For more information about
History Data, see
History Data
.
7.
Click Clear Display to clear the display of the status information in PC Panel
Communication Status.
8.
Click Close to close the Upload/Download dialog box after the upload/download process is
completed.
Table 6-1
Download Options
Options
Function
Point Programming
Downloads point programming information
to the fire panel.
DACT
Downloads DACT information to the fire
panel.
Event Codes
Downloads event information to the fire
panel.
Zones
Downloads zone information to the fire
panel.
System Programming
Downloads system programming informa-
tion to the fire panel.
Options
Downloads option modules information to
the fire panel.
ANN-Bus
Downloads ANN-Bus information to the fire
panel.
Date and Time
Downloads date and time information to the
fire panel.
•
You must enter the time in Download
Date and Time dialog box, to set the
download time.
•
Specify and/or verify the time, and
then click OK.