Fire-Lite PS Tools MS-9600 User Manual
Page 88

80
636 Pt Addr. Panel
PS-Tools
04/2010
Upload/Download Configuration Data
•
In the Event Codes tab, you can view the information such as values configured to 
upload or download, details on central station, event codes description, active value, 
and restoral.
2.Under Download to Panel, you can select any of the following configuration data option and then
click Download to Panel.
3.
Click Manual Evacuate to generate a Drill Activated Trouble at fire panel. The Drill Activated
trouble sounds all Silenceable devices and NACs connected to the FACP.
4.
Click Restore Evacuate to clear the Drill Activated trouble and restore the fire panel to Normal 
state. The sounding of the Silenceable devices and the NACs continues. Press Signal Silence 
button in the fire panel keypad to stop the sounders and NACs.
5.
Click Trouble Silence to silence all the trouble events in the fire alarm system.
6.
Click Clear History to clear all the History data in the fire panel. For more information about 
History Data, see 
History Data
.
7.
Click Clear Display to clear the display of the status information in PC Panel 
Communication Status.
8.
Click Close to close the Upload/Download dialog box after the upload/download process is 
completed. 
Table 6-1
Download Options
Options
Function
Point Programming
Downloads point programming information 
to the fire panel.
DACT
Downloads DACT information to the fire 
panel.
Event Codes
Downloads event information to the fire 
panel.
Zones
Downloads zone information to the fire 
panel.
System Programming
Downloads system programming informa-
tion to the fire panel.
Options
Downloads option modules information to 
the fire panel.
ANN-Bus
Downloads ANN-Bus information to the fire 
panel.
Date and Time
Downloads date and time information to the 
fire panel.
•
You must enter the time in Download
Date and Time dialog box, to set the 
download time. 
•
Specify and/or verify the time, and
then click OK.