Editing modules, Deleting modules – Fire-Lite PS Tools MS-9600 User Manual
Page 56
48
636 Pt Addr.Panel
PS-Tools
04/2010
Configuring Fire Panels
12. You can map each module to five Zones. Type the two digit number corresponding to the zone
assigned to the device for Zone 1 to Zone 5. The factory default for an unprogrammed device
is Z00 for a general alarm zone.
13. Type Additional Information about the module being programmed. This information is
displayed as part of the device label on the fire panel display.
14. Click OK. The module is added to the SLC loop setup.
Editing Modules
Using the Edit Device(s) option, you can edit the module type, module options, and the zone
mapping.
To edit the modules in the SLC loop
1.
Select the check box corresponding to the device you want to edit, in the SLC Loop Setup ->
Modules pane. You can select only one device at a time.
2.
Click Edit Device(s) to edit the device information. The Edit dialog box appears.
3.
Update the device information such as Device Type, Device Label, Device Options, and Zone
assignments.
4.
Click OK. The device information is updated in SLC loop setup.
Note
You cannot modify the loop and device address using the Edit Device(s) option.
Deleting Modules
When a module is no longer used, you can delete the module from the SLC Loop.