PS-Tools User Guide
636 Pt Addr. Panel
PS-Tools
04/2010
33
2.
Type the Maintenance password to change the factory set password for maintenance level
programming in the fire panel.
Note
Both Master and Maintenance passwords must consist of exactly 5 numbers.
Trouble Reminder
Click Trouble Reminder to enable the trouble reminder option. By default, this option is disabled.
Water Flow Devices Silenceable
Click Water Flow Devices Silenceable to enable the Water Flow Devices Silenceable option. By
default, this option is disabled.
Canadian Option Enabled
To configure Canadian Option
1.
Click Canadian Option Enabled.
a.
Ensure the input/output zone types are defined as in
b.
You can set the Auto Silence option for NACs, only to No AutoSilence or 20 minutes.
NACs, which are programmed as No AutoSilence, remain in the same mode when
Canadian Option is enabled.
If NAC is programmed for Auto Silence, the default time is 20 minutes. If you set the auto
silence time to a value such as 10 or 30 minutes, it is automatically reset to 20 minutes.
Table 5-1
Zone and Module types available for Canadian option
Module types blocked from selection
Changes to
Monitor
Pull Station
MON User defined 3
Pull Station
MON User defined 7, 8, 9, 13, 16, and 17
Supervisory
Medical, Hazard, and Tornado Alert
Supervisory
Supervisory AR (Non-Latching)
Supervisory
Process Monitor AR and Process Monitor
Supervisory
Drill Switch AR (Non-Latching)
Drill Switch