Ann-audio, Ann-bus address – Fire-Lite PS Tools MS-9600 User Manual
Page 46
38
636 Pt Addr.Panel
PS-Tools
04/2010
Configuring Fire Panels
ANN-AUDIO
The ANN-AUDIO 25/50 ZS All Call Zone series audio panel is used to play an audio message when
there is an alarm in one of the input zones. This audio panel connects to the FACP through the
ANN-BUS communication circuit.
You can select one of the five audio messages the audio panel plays, when an FACP input zone goes
into alarm. The message plays over the corresponding audio panel output circuit. The input zones can
be programmed as alarm type, supervisory type, process monitor type, or AC Loss Monitor.
Note
Ensure the input zone type is not Ack, Sil, Reset, or PAS Bypass switches.
Example: If FACP input zone 3 goes into alarm, the programmed message plays over the
ANN-AUDIO 25/50 ZS output circuit 3. If two or more input zones are active at the same time, the
highest priority message plays.
The connection between the fire panel and the ANN-AUDIO 25/50 ZS audio panel is accomplished
by a pair of communication wires connected between the A/B terminals on TB3 of the FACP and TB1
terminals 2 & 3 of the ACC-ZPMK module on the ANN-AUDIO 25/50 ZS.
ANN-BUS Address
ANN-BUS Address allows you to install the modules type in their respective 1-8 addresses.
To configure the ANN-BUS Address
1.
Click Next at the lower-right corner of the Global Options pane to view the Primary ANN Bus
pane or click ANN Bus Settings > Primary ANN Bus Settings in the left pane.