Configuring optional modules, Nal modules (see – Fire-Lite PS Tools MS-9600 User Manual
Page 43
PS-Tools User Guide
636 Pt Addr. Panel
PS-Tools
04/2010
35
Configuring Optional Modules
The optional modules installed in the 636 Pt Addr. system include ACM Series annunciators, graphic
and LCD annunciators.
Figure 5-6
Configuring Optional Modules
To configure the optional modules
1.
Click EIA-485 Terminal Mode Enabled, to enable the LCD-80F terminal mode annunciator.
This feature allows a series of up to 32 LCD-80F annunciators to be connected to the FACP’s
EIA-485 Terminal Mode connector.
2.
Click UDACT-F Communicator Installed, to allow a UDACT-F communicator to connect to
the FACP using the RS-485 ACS connector. If this feature is enabled, the reporting style for the
UDACT-F can be selected between point and zone.
3.
Click Annunciators, to allow a series of ACS annunciators, to be connected to the RS-485
ACS connector on the fire panel. If this feature is enabled, each ACS address can be
individually enabled/disabled.
4.
Click Save to Database to save the configuration in the PS-Tools database.
5.
Click Next in ANN-BUS or click Detectors in SLC Loop Setup in the left pane, to view the
SLC Loop Setup -> Detectors configuration pane.
6.
Click Prev to view the General System Settings pane for the 636 Pt Addr. system.