Loop style, Day light savings, Pc/printer installed – Fire-Lite PS Tools MS-9600 User Manual
Page 42: Banner display
34
636 Pt Addr.Panel
PS-Tools
04/2010
Configuring Fire Panels
Loop Style
In Loop 1 and Loop 2, select the wiring style for the loop. The wiring style can be Style 4 or Style 6.
The default wiring type is Style 4.
Day Light Savings
To configure the Day Light Savings feature
1.
Select the starting day and month in the Daylight Savings Time Starts list.
2.
Select the last day and month in the Daylight Savings Time Ends list (see
PC/Printer Installed
To program PC/Printer Installed option
1.
Select Printer No Supervision, if the printer connected to the fire panel does not require
supervision.
2.
Select Printer w/ Supervision, if the printer connected to the fire panel requires supervision.
3.
Click PC if only a computer is connected to the fire panel (see
4.
Select the Printer Baud rate if a printer is connected to the fire panel. The available options are
2400 bps, 4800 bps, or 9600 bps. This option is disabled if no printer is connected to the fire
panel.
Banner Display
To configure the banner settings
1.
In Banner Display, click User to use a custom display. You can type the banner display text in
Banner Text 1 and Banner Text 2.
2.
Click Factory option to display the default banner text when the fire panel is in Normal mode
of operation. (see
).
3.
Click Save to Database to save the configuration in the PS-Tools database.
4.
Click Next or click Optional Modules in the left pane, to view the Optional Modules
configuration pane.
5.
Click Prev to view the settings for NAC 4.
Zone types blocked from selection
Changes to
AR(auto-resettable) Supervisory
Supervisory
Drill Switch AR
Drill Switch
Process monitor, hazard, tornado, and medical alert
Supervisory