636 Pt Addr.Panel
PS-Tools
04/2010
Configuring Fire Panels
Relay
The fire panel consists of one fixed and two programmable Form-C dry contact relays. The fixed
fail-safe relay monitors system troubles. The two programmable relays are factory default. They can
be programmed for system alarm and system supervisory, and configured for the following
operations.
•
Fire alarm
•
Trouble
•
Supervisory
•
Supervisory auto-resettable
•
DACT communication failure
•
Process monitor
•
Process monitor auto-resettable
•
Hazard alert
•
Medical alert
•
AC loss.
To configure the relays
1.
Under Relays, select the type for Relay 1 from the drop-down list.
By default, Relay 2 is disabled and set to Trouble.
2.
Select the type for Relay 3. (see
Zones
In the input/output zones configuration, you can specify the zone type only if a DACT programmed
for zone reporting, is installed on the fire alarm control panel.
To configure each zone
1.
Under Zones, select the Zone Type from the list. Selecting WATERFLOW option assigns a
Waterflow silenceable zone type to the selected zone. Any signaling devices programmed to
the same zone can be silenced by pressing the Alarm Silence key or by using the Auto-silence
feature.
2.
Under Enabled/Disabled, select Enable to enable the zone. If you select Disable, the zone is
disabled by the fire panel, preventing the zone circuit from reporting alarms and troubles to the
panel. Disabling a zone disables all the functionalities associated with that zone.
Note
Programming the Zone Message is not supported in this release.
Special Zones
The zones 97, 98, and 99 can be programmed for normal zone operation or for special purpose
applications. If the zones are not selected, they are assigned to input and output devices.