Section 8
Reporting
This section lists receivers that are compatible with this control panel, and the reporting codes
sent by the control panel for SIA and Contact ID formats.
8.1
Receivers Compatible with the Control Panel
Table 8-1 shows receivers compatible with the control panel.
Table 8-1: Receivers Compatible with the Control Panel
8.2
Reporting Formats Dialer Outputs
Manufacturer
Model
Format
Silent Knight
Model 9800
SIA and Contact ID
Model 9000 (SIA formats)
SIA
Ademco
Model MX8000 (Contact ID)
Contact ID
Sur-Gard
SG-MLR2-DG (V. 1.64 or higher)
SIA and Contact ID
Osborne Hoffman
Quickalert
SIA and Contact ID
SIA Reporting Format
Contact ID Reporting Format
Event Description
Event
Family
Event Class
(System, Zone,
or Point)
Module
ID #
(if any)
SIA
Event
Code
Parameter
(if any)
Qualifier
Event
Code
Group
#
Contact
#
System Events
System events are reported when either “Report by Zone” is selected.
AC power restore
Trouble
System Event
AR
3
301
00
000
AC power lost
Trouble
System Event
AT
1
301
00
000
Short circuit removed from SLC communi-
cation loop
Trouble
System Event
ER
33
3
332
00
Exp. ID
Short circuit detected on SLC communica-
tion loop
Trouble
System Event
ET
33
1
332
00
Exp. ID
Fire drill has begun
Test
System Event
FI
1
604
00
000
Fire drill ended
Test
System Event
FK
3
604
00
000
Panel date has been changed
Trouble
System Event
JD
1
625
00
000
Panel time has been changed
Trouble
System Event
JT
1
625
00
000
Local programming begin
Trouble
System Event
LB
1
627
00
000