2 control panel programming, 3 default control panel configuration, 1 default mapping of slc inputs to outputs – Fire-Lite MS-25E Addressable Fire Control Panel User Manual
Page 60: 2 mapping of slc inputs to outputs, Control panel programming -2, Default control panel configuration -2
Model MS-25 Installation and Operation Manual
6-2
53688
6.2
Control Panel Programming
The MS-25 is an addressable control panel that has the characteristics of a 5 zone
conventional fire alarm control panel.
6.3
Default Control Panel Configuration.
The panel ships from the factory in a defaulted configuration that may allow the installer to
use the panel without doing any custom programming.
6.3.1
Default Mapping of SLC Inputs to Outputs
The panel mapping configuration for the MS-25 is fixed with regards to SLC addresses, zone
assignments and output points. The relationship between input points and output points
follows the rules defined in 6.3.2 below. For input points, the SLC address determines the
zone assignment and alarm characteristics. For output points, the SLC address determines the
output function for the point.
6.3.2
Mapping of SLC Inputs to Outputs.
Table 6-2: Input Points
INPUT POINTS
Zone
Input Point Types
Function
Qty
Start
SLC ID
End SLC
ID
Description
Zone 1
HFS-P, HFS-PT, HFS-D,
HFS-T, SD355, SD355T,
D355PL, H355, MMF-301,
BG-12LX, HFS-MM
Alarm
15
1
15
Alarm Zone 1
Supervisory 5
16
20
Supervisory Zone 1
Zone 2
HFS-P, HFS-PT, HFS-D,
HFS-T, SD355, SD355T,
D355PL, H355, MMF-301,
BG-12LX, HFS-MM
Alarm
15
21
35
Alarm Zone 2
Supervisory 5
36
40
Supervisory Zone 2
Zone 3
HFS-P, HFS-PT, HFS-D,
HFS-T, SD355, SD355T,
D355PL, H355, MMF-301,
BG-12LX, HFS-MM
Alarm
15
41
55
Alarm Zone 3
Supervisory 5
56
60
Supervisory Zone 3
Zone 4
HFS-P, HFS-PT, HFS-D,
HFS-T, SD355, SD355T,
D355PL, H355, MMF-301,
BG-12LX, HFS-MM
Alarm
15
61
75
Alarm Zone 4
Supervisory 5
76
80
Supervisory Zone 4
Zone 5
HFS-P, HFS-PT, HFS-D,
HFS-T, SD355, SD355T,
D355PL, H355, MMF-301,
BG-12LX, HFS-MM
Alarm
15
81
95
Alarm Zone 5
Supervisory 5
96
100
Supervisory Zone 5