5 addressing slc devices, Addressing slc devices -6 – Fire-Lite MS-25E Addressable Fire Control Panel User Manual
Page 58
Model MS-25 Installation and Operation Manual
5-6
53688
5.5
Addressing SLC Devices
All SLC devices are addressed using the two rotary dials that appear on the device board. Use
the ONES rotary dial to set the ones place in a one or two digit number, and use the TENS
rotary dial to set the tens place in a two digit number.
Example 1: To select device address 35, turn the ONES rotary dial to 5 and the TENS rotary
dial to 3 as shown in Figure 5-4.
Example 2: To select device address 105, turn the ONES rotary dial to 5 and the TENS rotary
dial to 10 as show in Figure 5-4.
Figure 5-4 SLC Device Addressing Using Rotary Dials
All dials labeled for ONES
or TENS position
Example 1: Device Set to 35
Example 2: Device set to 105