Table 6-2 shows that any input SLC device with an address set within the range 1-15 will be
assigned to zone 1 as an alarm input type. An SLC output relay point assigned to address 111
or 112 will activate for an alarm in zone 1.
6.3.3
Default Mapping for the 2 built-in Notification
Circuits.
There are 2 built-in notification circuits (NAC 1 and NAC 2). They are both defaulted to
activate when any of the 5 zones are in alarm. When active, NAC 1 and NAC 2 will sound the
System Sensor synchronization pattern. To change the behavior of the default mapping of
these circuits refer to Section 6.5.
Table 6-3: Output Points
OUTPUT POINTS
Group
Output Point Type
Qty
Start SLC
ID
End SLC
ID
Output Activates For
OPG 1
HFS-MR, CRF-300, CRF-300A
2
111
112
Zone 1 Alarm
OPG 2
HFS-MR, CRF-300, CRF-300A
2
113
114
Zone 2 Alarm
OPG 3
HFS-MR, CRF-300, CRF-300A
2
115
116
Zone 3 Alarm
OPG 4
HFS-MR, CRF-300, CRF-300A
2
117
118
Zone 4 Alarm
OPG 5
HFS-MR, CRF-300,CRF-300A
2
119
120
Zone 5 Alarm
OPG 6
HFS-MR, CRF-300, CRF-300A
2
121
122
Zone 1 Supervisory
OPG 7
HFS-MR, CRF-300, CRF-300A
2
123
124
Zone 2 Supervisory
OPG 8
HFS-MR, CRF-300, CRF-300A
2
125
126
Zone 3 Supervisory
OPG 9
HFS-MR, CRF-300, CRF-300A
2
127
128
Zone 4 Supervisory
OPG 10
HFS-MR, CRF-300, CRF-300A
2
129
130
Zone 5 Supervisory
OPG 11
HFS-MR, CRF-300, CRF-300A
2
131
132
Zone 1 Trouble
OPG 12
HFS-MR, CRF-300, CRF-300A
2
133
134
Zone 2 Trouble
OPG 13
HFS-MR, CRF-300, CRF-300A
2
135
136
Zone 3 Trouble
OPG 14
HFS-MR, CRF-300, CRF-300A
2
137
138
Zone 4 Trouble
OPG 15
HFS-MR, CRF-300, CRF-300A
2
139
140
Zone 5 Trouble
OPG 16
HFS-MR, CRF-300, CRF-300A
2
141
142
General Alarm
OPG 17
HFS-MR, CRF-300, CRF-300A
2
143
144
General
Supervisory
OPG 18
HFS-MR, CRF-300, CRF-300A
2
145
146
General Zone Trouble
OPG 19
HFS-MR, CRF-300, CRF-300A
2
147
148
General Trouble
OPG 20
HFS-MR, CRF-300, CRF-300A
2
149
150
Alarm Silenced
OPG 21
HFS-MR, CRF-300, CRF-300A
2
151
152
Trouble Silenced
OPG 22
HFS-MR, CRF-300, CRF-300A
2
153
154
AC Loss
OPG 23
HFS-MR, CRF-300, CRF-300A
2
155
156
Resettable Aux Relay
OPG 24
HFS-MR, CRF-300, CRF-300A
2
157
158
Aux Door Holder