3 ulc requirements, Ulc requirements -4 – Fire-Lite MS-25E Addressable Fire Control Panel User Manual
Page 20
Model MS-25 Installation and Operation Manual
2-4
53688
2.2.2
Requirements for Central Station Fire Alarm
Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the MS-25 sends an automatic
daily test to the central station.
3. The AC Loss Hours option must be set from 1-3 hours.
2.2.3
Requirements for Local Protected Fire Alarm
Systems
At least one UL listed supervised notification appliance must be used.
2.2.4
Requirements for Remote Station Protected Fire
Alarm Systems
1. Do not exceed the current load restrictions shown in Section 3.6.
2. The AC Loss Hours option must be set from 1-3 hours.
2.3
ULC Requirements
Install in accordance with the Canadian Electrical Code, C22.1, Part 1, Section 32.