Section 1 introduction, 1 overview of basic system, 1 hardware features – Fire-Lite MS-25E Addressable Fire Control Panel User Manual
Page 11: 2 software features, Overview of basic system -1, 1 hardware features -1 1.1.2 software features -1
53688
1-1
Section 1
Introduction
The MS-25 Fire Alarm Control / Communicator is an addressable fire control system that
meets the requirements of UL 864, ULC 527, and ULC 559. Unless otherwise indicated, all
references to MS-25 also refer to MS-25C and MS-25E.
1.1
Overview of Basic System
1.1.1
Hardware Features
•
The MS-25 has one signaling line circuit (SLC) that supports 25 SLC devices (See
Section 5.1), and one SBUS circuit that supports two remote annunicators.
•
2.0A of output power is available through 2 sets of terminals for notification appliance
circuits or 1.0A for auxiliary power applications. Each circuit is power limited per UL 864
and can source up to 2.0A.
Note: Total output power for all three circuits must not exceed 2.0A.
•
Built-in dual phone line, digital alarm communicator/transmitter (DACT).
•
Reports events to central station by zone.
•
Two general purpose Form C programmable relays.
•
One Form C Trouble Relay.
1.1.2
Software Features
•
The MS-25 is an addressable panel that operates like a 5 zone conventional panel.
•
Advanced addressable smoke detector features:
–Automatic drift compensation
–Maintenance alert region
–Point status meets calibrated smoke test requirements for NFPA 72
•
Auto learn “JumpStart” feature for easy programming.
•
A choice of output patterns available for notification outputs, including ANSI 3.41
temporal signal.
•
Built-in synchronization appliance support for Amseco, Gentex
®
, Wheelock
®
, or System
Sensor
®
.