Model MS-25 Installation and Operation Manual
3-2
53688
3.3
Electrical Specifications
Table 3-1 list the electrical specifications for the MS-25 field wiring as well as a description of
the each individual terminal and their respective electrical rating. For location of the terminals
refer to 3.5. See also Section 4 for installation.
*
Regulated for NAC circuits
*
Special application when used for auxiliary power circuits.
Table 3-1: Terminal Descriptions
Terminal
Block
Label
Description
Rating
Earth Ground
Fault Impedance
Group
Individual
Voltage
Current
Ohms
TB 1
SBUS
–
SBUS Power
27.4 VDC
100 mA
0
Ω
+
A
SBUS Communication
3.3 VDC
10 mA
0
Ω
B
SLC Out
–
SLC Terminals
24 VDC
100 mA
0
Ω
+
*NAC1
–
Notification Appliance Circuit 24 VDC
2.0 Amp
0
Ω
+
Auxiliary power
1.0 Amp
*NAC2
–
Notification Appliance Circuit 24 VDC
2.0 Amp
0
Ω
+
Auxiliary power
1.0 Amp
TROUBLE NO
Normally open relay contact
24 VDC
2.5 A, resistive
N/A
COM
Common terminal
NC
Normally closed relay contact
RELAY 1
NO
Normally open relay contact
24 VDC
2.5 A, resistive
N/A
COM
Common terminal
NC
Normally closed relay contact
RELAY 2
NO
Normally open relay contact
24 VDC
2.5 A, resistive
N/A
COM
Common terminal
NC
Normally closed relay contact
TB 2
TELCO 1
RING
Phone Line 1 Telco Ring
N/A
N/A
N/A
TIP
Phone Line 1 Telco Tip
PHONE 1
RING
Phone Line 1 Phone Ring
TIP
Phone Line 1 Phone Tip
TELCO 2
RING
Phone Line 2 Telco Ring
TIP
Phone Line 2 Telco Tip
PHONE 2
RING
Phone Line 2 Phone Ring
TIP
Phone Line 2 Phone Tip