21 basic operation, 1 conduct a fire drill, 2 conduct an indicator test – Fire-Lite MS-25E Addressable Fire Control Panel User Manual
Page 77: 3 silence alarms or troubles, 4 reset alarms, 5 view alarms or troubles, Basic operation -7
System Operation
53688
7-7
7.21 Basic Operation
7.21.1 Conduct a Fire Drill
1. Activate the key by turning it to the ON position.
2. Press and hold the Drill key for 2 seconds.
3. The drill will begin after the key has been held down for 2 seconds.
4. Press the Reset key to end the Fire Drill. (If you do not press the Reset Key to end the Fire
Drill manually, it will time out automatically after 10 minutes).
7.21.2 Conduct an Indicator Test
The indicator test checks the annunciator LEDs, PZT, and LCD display.
1. Activate the key by turning it to the ON position.
2. Press the Reset Key to conduct an indicator test. The system turns on all LEDs for several
seconds, beeps the PZT, and displays a message on the LCD display. A problem is
indicated if any of the following occurs:
•
An LED does not turn on.
•
You do not hear the beep.
•
The LCD is unable to annunciate the message correctly.
7.21.3 Silence alarms or troubles
1. Activate the key by turning it to the ON position.
2. Press the Silence Key.
Note: Alarm and trouble signals that have been silenced but the detector remains un-restored and will un-silence
every 24 hours until it is restored.
7.21.4 Reset alarms
1. Activate the key by turning it to the ON position.
2. Press the Reset key.
7.21.5 View Alarms or Troubles
When the system is in alarm or trouble, you can press the Down key to view the location of an
alarm or trouble. The Point ID, and time stamp of when the condition occurred will also be
displayed.