Edwards Signaling 102 DeviceNet User Manual
Page 6
P/N 3100125 ISSUE 3
PAGE 6
For Units Configured with 1 Light Module
BYTE
BIT7
BIT6
BIT5
BIT4
BIT3
BIT2
BIT1
BIT0
0
DON'T
DON'T
DON'T
DON'T
DON'T
DON'T
DON'T
LMP 1
CARE
CARE
CARE
CARE
CARE
CARE
CARE
1 = ON
0 = OFF
1
0
0
1
DON'T
DON'T
DON'T
DON'T
LMP 1
45
CARE
CARE
CARE
CARE
1 = FLSH
FPM
0 = STDY
1
0
1
0
DON'T
DON'T
DON'T
DON'T
LMP 1
60
CARE
CARE
CARE
CARE
1 = FLSH
FPM
0 = STDY
1
1
DON'T
DON'T
DON'T
DON'T
DON'T
DON'T
LMP 1
80
CARE
CARE
CARE
CARE
CARE
CARE
1 = FLSH
FPM
0 = STDY
1
0
0
0
DON'T
DON'T
DON'T
DON'T
LMP 1
80 FPM
80 FPM
80 FPM
CARE
CARE
CARE
CARE
1 = FLSH
DEFLT
DEFLT
DEFLT
0 = STDY
2
DON'T
DON'T
DON'T
DON'T
Sounder
Tone
Tone
Tone
CARE
CARE
CARE
CARE
1 = ON
MSB
LSB
0 = OFF
2.0
Standard Objects.
2.1
Identity Object (Class ID = 1).
There is a single instance of the identity object for the Triliptical DeviceNet Stackable Beacon. No class attributes
are supported. All of the instance attributes are contained in rom and are gettable but not settable. The table
below shows the values.
ATTRIBUTE
ACCESS
DATA
ID
RULES
NAME
TYPE
VALUE
1
Get
Vendor Code
Uint
0x201 (513)
2
Get
Product Type
Uint
0x0000
3
Get
Product Code
Uint
0x0001
4
Get
Revision
Word
01.01
5
Get
Status
UDINT
0x0000
6
Get
Serial #
Uint
UNIQUE SERIAL #
7
Get
Product Name
STRUCT
102
Identity Object Services:
SERVICE
SERVICE CODE
PARAMETERS
Get Attribute Single
0x0E
Attribute ID
Reset
0x05
0, 1
2.2
Message Router Object (Class ID = 2).
There is no externally visible interface to the Message Router Object.
2.3
DeviceNet Object (Class ID = 3).
There is a single instance of the DeviceNet Object for the Triliptical DeviceNet Stackable Beacon.
DeviceNet Object Class Attributes:
ATTRIBUTE
ACCESS
DATA
ID
RULES
NAME
TYPE
VALUE
1
Get
Revision
Uint
0x0002