6 firmware upgrade – Detcon 1600A-N1R User Manual
Page 29
1600A-N1R
1600A-N1R Instruction Manual
Rev. 0.1
Page 25 of 38
Bit 3
1 = Channel 4 Alarm 2
0 = Channel 4 no Alarm 2
Bit 2
1 = Channel 3 Alarm 2
0 = Channel 3 no Alarm 2
Bit 1
1 = Channel 2 Alarm 2
0 = Channel 2 no Alarm 2
Bit 0
1 = Channel 1 Alarm 2
0 = Channel 1 no Alarm 2
40019 Alarm 3 Status Bits
High Byte
Bit 7
1 = Channel 16 Alarm 3
0 = Channel 16 no Alarm 3
Bit 6
1 = Channel 15 Alarm 3
0 = Channel 15 no Alarm 3
Bit 5
1 = Channel 14 Alarm 3
0 = Channel 14 no Alarm 3
Bit 4
1 = Channel 13 Alarm 3
0 = Channel 13 no Alarm 3
Bit 3
1 = Channel 12 Alarm 3
0 = Channel 12 no Alarm 3
Bit 2
1 = Channel 11 Alarm 3
0 = Channel 11 no Alarm 3
Bit 1
1 = Channel 10 Alarm 3
0 = Channel 10 no Alarm 3
Bit 0
1 = Channel 9 Alarm 3
0 = Channel 9 no Alarm 3
Low Byte
Bit 7
1 = Channel 8 Alarm 3
0 = Channel 8 no Alarm 3
Bit 6
1 = Channel 7 Alarm 3
0 = Channel 7 no Alarm 3
Bit 5
1 = Channel 6 Alarm 3
0 = Channel 6 no Alarm 3
Bit 4
1 = Channel 5 Alarm 3
0 = Channel 5 no Alarm 3
Bit 3
1 = Channel 4 Alarm 3
0 = Channel 4 no Alarm 3
Bit 2
1 = Channel 3 Alarm 3
0 = Channel 3 no Alarm 3
Bit 1
1 = Channel 2 Alarm 3
0 = Channel 2 no Alarm 3
Bit 0
1 = Channel 1 Alarm 3
0 = Channel 1 no Alarm 3
40020 Cal Status Bits
High Byte
Bit 7
1 = Channel 16 Cal
0 = Channel 16 no Cal
Bit 6
1 = Channel 15 Cal
0 = Channel 15 no Cal
Bit 5
1 = Channel 14 Cal
0 = Channel 14 no Cal
Bit 4
1 = Channel 13 Cal
0 = Channel 13 no Cal
Bit 3
1 = Channel 12 Cal
0 = Channel 12 no Cal
Bit 2
1 = Channel 11 Cal
0 = Channel 11 no Cal
Bit 1
1 = Channel 10 Cal
0 = Channel 10 no Cal
Bit 0
1 = Channel 9 Cal
0 = Channel 9 no Cal
Low Byte
Bit 7
1 = Channel 8 Cal
0 = Channel 8 no Cal
Bit 6
1 = Channel 7 Cal
0 = Channel 7 no Cal
Bit 5
1 = Channel 6 Cal
0 = Channel 6 no Cal
Bit 4
1 = Channel 5 Cal
0 = Channel 5 no Cal
Bit 3
1 = Channel 4 Cal
0 = Channel 4 no Cal
Bit 2
1 = Channel 3 Cal
0 = Channel 3 no Cal
Bit 1
1 = Channel 2 Cal
0 = Channel 2 no Cal
Bit 0
1 = Channel 1 Cal
0 = Channel 1 no Cal
5.6 Firmware Upgrade
The 1600A-N1P is capable of firmware upgrades for both the PLC and touch screen device. Upgrades will be
performed by the user. The following components are needed to perform firmware upgrades:
o
ProSave Software (can be Downloaded free at http://www.siemens.com)
o
S7-200 USB PPI cable
o
S7-200 Memory cartridge
o
DB9 Gender Changer