Detcon 1600A-N1R User Manual
Page 21
1600A-N1R
1600A-N1R Instruction Manual
Rev. 0.1
Page 17 of 38
Figure 23 Accessing Serial Setup
Figure 24 Serial Setup screen
Addressing Serial Sensors
When connecting to a Detcon Model 600 or Model 700 Series sensor, the addressing procedure is different.
First, note how the gas sensors are addressed. Each sensor must be set to a different address. The addresses
start from 01 and count up to 16 (hex 10). An example is shown below to explain the procedure. To address
the gas sensors, set the following:
CH #
Sensor Address
CH #
Sensor Address
01
01
Hex
09
09
Hex
02
02
Hex
10
0A
Hex
03
03
Hex
11
0B
Hex
04
04
Hex
12
0C
Hex
05
05Hex
13
0D
Hex
06
06
Hex
14
0E
Hex
07
07
Hex
15
0F
Hex
08
08
Hex
16
10
Hex
NOTE: the CH# is the gas channel number displayed on the Main Display. The sensor address is the
serial ID address (in Hexadecimal) set at the 600 or 700 Series sensor.
NOTE: The 1600A Device # is in decimal format, and the serial address switch setting for the 600 or 700
Series Sensor is in hexadecimal format. This means that device number 10 decimal on the 1600A
corresponds to the 600 or 700 Series Sensor at address 0A hexadecimal.