Curtain operation during back-up, Setting scs™ back-up stage jumpers, Changing the scs™ curtain back-up stage – Hired-Hand Farm Hand Series: SCS w/Back-Up User Manual

Page 10

background image

Part No. 4801-5117 Rev. 8-01

Farm Hand SCS

8

To Back-

up Relay

hand the Fail-Safe relay strip would close each of the relays in the strip resulting in energizing the
ventilators in case of a controller power failure. Each of the relay strips contains four relays for
controlling four stages. In the SCS™ 16 there are a total of four relay strips, three will be N.O. and
one will be a Fail-Safe. In the SCS™ 8 there are two relay strips. One is a N.O. and one is a Fail-
Safe strip. The operator must insure that the Fail Safe relay strip is connected only to stages that
should be turned on in case of a controller failure. See Section 18 for a physical description of the
relay strips. It is not recommended to place heating equipment on Fail-Safe stages.

9. Curtain Operation During Back-up

The SCS contains a relay that can operate the curtains during Back-up operation of the SCS. The
curtains will automatically open during back-up based upon the selection of the back-up stage, either
COOL1, COOL2 or COOL 3. The SCS is shipped from the manufacturer with the Curtains connected
to the COOL 1 Stage. To change the Cool stage see Section 11.

10. Setting SCS™ Back-Up Stage Jumpers

Pictured at the right is a Stage Relay Board consisting of four stage relays and the associated stage
jumper for each stage relay. The stage jumpers a
labeled COOL 1, COOL 2, COOL 3 and HEAT.
Location of the jumper places the stage in one of
these four modes, or if the jumper is not inserted, the
stage is not placed on Back-Up. The jumpers
should be placed based on the operation of stage
equipment and should be the same as assigned in the
Master Controller. Jumpers are placed according the
following table:

Type of Stage

Operation

Jumper

Assignment

Cool Negative Fan

COOL 1

Cool Negative

Tunnel Fan

COOL 2

Cool Tunnel Fan

COOL 3

Heat Stage

HEAT

Stage not on Back-

Up

No Jumper

Installed


11. Changing the SCS™ Curtain Back-Up Stage

At the top of the SCS relay board is a terminal strip labeled BACKUP
SYSTEM. Connect the jumper to the appropriate Stage, either COOL
1, COOL 2 or COOL 3. The SCS system is sent from the manufacturer
with the Backup curtain connection to COOL 1.











Stage

Jumpers

STAGE RELAY BOARD

Stage Relay

Stage

Harness

connector

cables to

Terminal

Block