You can calculate your power requirements by combining the power demands for the various modules and fan units
in your configuration. While you may use fewer ports in a given line card, it is always safer to use the power
requirement of a fully populated card.

CAUTION
For the NEBS-compliant installation of a Brocade VDX 8770-8 with AC or DC systems, use a ground wire
of at least 2 AWG. The ground wire should have an agency-approved crimped connector (provided with
the device) attached to one end, with the other end attached to building ground. The connector must be
crimped with the proper tool, allowing it to be connected to both ground screws on the enclosure. Before
crimping the ground wire into the provided ground lug, ensure that the bare copper wire has been
cleaned and antioxidant is applied to the bare wire.

Environmental requirements

DANGER

Do not install the router in an environment where the operating ambient temperature might
exceed 40°C (104°F).

Table 4

lists the environmental operating ranges for the Brocade VDX 8770-8. The requirements for non-operating

conditions are also provided for acceptable storage and transportation environments.

TABLE 3

Power demands per component

Module or fan units

Power demand at idle -
blades enabled, no
optics, ports disabled
(Watts)

Nominal power demand -
blades enabled, optics, 50%
line rate, random packets
(Watts)

Maximum power demand - blades
enabled, optics, traffic present, full line
rate, 64 byte smallest packet, 40°C
ambient temp., maximum power for all
supported optics (Watts)

Management module 46

46

50

Switch fabric module

120

120

132

48x1G line card

245

310

460

48x10G line card

245

310

460

12x40G line card

247

290

440

Fan unit

25

25

268

TABLE 4

Environmental requirements

Condition

Acceptable range during operation

Acceptable range during non-operation

Ambient temperature

0

°

to 40

°

C (32

°

to 104

°

F) outside

switch

-25

°

to +70

°

C (-13

°

to 158

°

F) outside

switch

Humidity

5% to 90% RH noncondensing, at 40

° C

(104

°

F), with maximum gradient of 10%

per hour

10% to 90% RH noncondensing, at 70

°

C

(158

°

F)

Altitude

0 to 3 km (10,000 ft.) above sea level

0 to 12 km (40,000 ft.) above sea level