Daily report – Yokogawa DA100 User Manual
Page 76

IM DA100-11E
7-11
Output Format
7
Daily Report
The daily report is output in the following format with the command, TS4+device trigger(GET)+RF1.
Data
length
Year Month Day
Hour Minute 0
A1 B1
C1
D1
An Bn
Cn
Dn
Number of output bytes
Time when the report is created
First channel
Last channel
A1 to An: Report channel number ( 00H to 3BH)
B1 to Bn: Unit number (Fixed to 80H during computation)
C1 to Cn: Channel number*
D1 to Dn: Report computation type
*: Computation channels are
00H to 1DH for stand-alone type
00H to 3BH for extended type
0
Extension
number
Power failure data 0: no failure 1:failure occurred
0 or 1
A1
An
A1
An
A1
An
E1
F1
G1
DATA H1
En
Fn
Gn
DATA Hn
E1
F1
I1
DATA J1
DATA Jn
E1
F1
K1
DATA L1
DATA Ln
En
Fn In
En
Fn
Kn
Report computation data for each report channel
A1 ot An: Report channel number : 00H to 3BH
E1 to En:
Type of the report computation result to output
F1 to Fn: Report computation data status
G1 to Gn, l1 to ln, K1 to Kn:
Mantissa of the report computation data
Data H1 to data Hn:
Mantissa of the report computation data
Data J1 to data Jn:
Mantissa of the report computation data
Data L1 to data Ln:
Mantissa of the report computation data
Starting date and time of the sum for TOTAL
Instantaneous value, average value
or summed value
Minimum value or Total of
the summed values
Maximum value
Year Month Day
Hour Minute
The meaning of each data is the same as the hourly report.
Note
• RF1 outputs data on the specified report channels.
7.9 Report Output Format