Xi sets the a/d integration time, Xq sets the filter, Xa performs the setting related to alarm – Yokogawa DA100 User Manual
Page 59: Xy sets the re-alarm for a re-failure, Xn sets and/or of the alarm output relay, Xd sets energizing or deenergizing, Xh sets the hold/non-hold, Xb sets the burnout

IM DA100-11E
6-7
Commands
6
Integration time: Equivalent to 50/60 Hz
Input module
Filter off
Filter on
10CH
0.5*
3
20CH
2
4
30CH
2
4
*: 2s if the power monitor module is installed
Integration time: 100 ms
Input module
Filter off
Filter on
10CH
4
12
20CH
5
15
30CH
6
20
XI
Sets the A/D integration time.
Mode
Setup mode
Setting
XIp1, p2
p1
Subunit (0 to 5)
p2
Integration time (AUTO, 50 Hz, 60 Hz,
100 ms)
Example
Set the A/D integration time in subunit 0 to 50
Hz.
XI0, 50Hz
XQ
Sets the filter.
Mode
Setup mode
Setting
XQp1
p1
ON
Filter on
OFF
Filter off
Example
Insert a filter in the input.
XQON
XA
Performs the setting related to alarm.
Mode
Setup mode
Setting
XAp1, p2, p3
p1
Interval for limit of increasing rate-of-
change (1 to 15)
p2
Interval for limit of decreasing rate-of-
change (1 to 15)
p3
Alarm hysteresis (0.0 to 1.0)
Example
Set the interval for limit of increasing rate-of-
change to 10, the interval for the limit of the
decreasing rate-of-change to 10 and alarm
hysteresis to 0.5%.
Comments
• This command sets an interval to detect the rate-
of-change alarm and hysteresis.
• Set an interval using the measurement period
as the unit.
• Set the hysteresis with the percentage of the
measurement range or scaling range.
• The computation channel hysteresis is fixed to
0.
XY
Sets the re-alarm for a re-failure.
Mode
Setup mode
Setting
XYp1, p2
p1
Reflash number (1 to 6)
p2
Off, subunit (I, 0 to 5) + relay number
Example
Set reflash relay 1 to relay module 1 connected to
slot 0 of the main unit.
XY1, I01
XN
Sets AND/OR of the alarm output relay.
Mode
Setup mode
Setting
XNp1, p2
p1
Unit
I: Main unit (DA100)
0 to 5: Subunit
p2
Relay number to be set to AND (01 to 60)
NONE: All are OR.
01-XX (XX=01 to 60)
Relays whose numbers are 1 to XX are
set to AND.
Example
Have No. 1 of slot 0 to No. 10 of slot 2 in the
alarm output relay module connected to the main
unit be AND relay outputs.
XNI, I, 01-20
Comments
• Setting is effective only in the same unit.
• Set p2 with the first relay number (01=fixed)
to the last relay number. If all OR output is to
be set, set p2 to NONE.
An error will occur when alarm output module or
DI/DO module isn’t mounted to selected DA100
or DS400/DS600.
XD
Sets energizing or deenergizing.
Mode
Setup mode
Setting
XDp1, p2
p1
Unit (I, 0 to 5) + Relay number (01 to 60)
p2
Selection of energizing/deenergizing
ENERG
Energizing
DE-EN
Deenergizing
Example
Set the relays of No. 1 in slot 0 to No. 10 in slot 5
of the relay module connected to subunit 5 to
energizing outputs.
XD501-60, ENERG
Comments
• If a successive number of output relays are to
be set, insert a minus sign (-) between the first
relay number and the last relay number, as
shown in the example. However, relays that
can be successively set are those in the same
subunit.
An error will occur when alarm output module or
DI/DO module isn’t mounted to selected DA100
or DS400/DS600.
XH
Sets the hold/non-hold.
Mode
Setup mode
Setting
XHp1
p1
Output relay hold on/off
ON
Hold
OFF
Non-hold
Example
Hold the output state of an alarm output relay.
XHON
XB
Sets the burnout.
Mode
Setup mode
Setting
XBp1, p2
p1
Channel number (001 to 560)
p2
Selection of burnout
OFF
UP
Upscale travelling beyond
the scale
DOWN
Downscale travelling
beyond the scale
Example
Set channels 01 to 10 of subunit 0 to upscale
burnout.
XB001-10, UP
Comments
• If channels are to be set successively, the setting
is effective only when they are in the same unit.
6.1 Setting Command