6.1 Setting Command

SL

Sets an event/action.

Mode

Operation mode

Release of event/action setting

Setting

SLp1, p2

p1 event/action box number (01 to 30)
p2 NONE

Event action setting by an alarm

Setting

SLp1, p2, p3, p4, p5

p1 Event action box number (01 to 30)
p2 Event (ALARM)
p3 Action mode (EDGE, LEVL)
p4 Action

ALARM_ACK

Acknowledgement of
alarm status.

ALARM_RST

Alarm reset

TIMER_RST

Timer reset

MATH

Computation start/stop/

reset/clear/group reset

REPORT

Report start/stop

FLAG

Set flag to 1

p5 Auxiliary action information (for
p3=EDGE)

For p4=MATH

START

Computation starts.

STOP

Computation stops.

RESET

Computed data are reset.

CLEAR

Computed data are cleared.

RST_G01 to RST_G07

Computed data in the specified
group are clear.

For p4=REPORT

START

Report starts.

STOP

Report stops.

For p4=FLAG

F01 to F16:Specified flag number is set to 1.

p5 Auxiliary action information (for
p3=EDGE)

For p4=FLAG

F01 to F16:Specified flag number is set to 1.

Event function setting by a remote, relay, timer, or
match time event

Setting

SLp1, p2, p3, p4, p5, p6

p1 Event action box number (01 to 30)
p2 Event (REMOTE, RELAY, TIMER,
MATCH_TIME)
p3 Auxiliary event information

For p2=REMOTE, contact number (1 to 12)

For p2=RELAY, the base unit + relay

number

For p2=TIMER, timer number (1 to 6)

For p2=MATCH_TIME, match time

number (1 to 3)

p4 Action mode (EDGE, LEVL)
p5 Action

ALARM_RST

Alarm reset

TIMER_RST

Timer reset

MATH

Computation start/stop/

reset/clear/group reset

REPORT

Report start/stop

FLAG

Set flag to 1

p6 Auxiliary action information

For p5=MATH

START

Computation starts.

STOP

Computation stops.

RESET

Computed data are reset.

CLEAR

Computed data are cleared.

RST_G01 to RST_G07

Computed data in the specified
group are clear.

For p5=REPORT

START

Report starts.

STOP

Report stops.

For p5=FLAG

F01 to F16:Specified flag number is set to 1.

Example

Set an event action to start coputation when an
alarm occurs in event action box 02.

SL02, ALARM, EDGE, MATH, START

Comments

• With an action as the start (event), another

action (action) can be executed automatically.

• Thirty types of event actions can be set.
• If the action mode is EDGE, the set action

continues even if the event action is over.

• If the action mode is set to LEVL , the set action

continues from the first event occurrence to the
next event occurrence.

• If the avtion mode is set to LEVL , the start/

stop/clear & start computation are disable.

• If the action is set to MATH, the edge and level

action cannot be set simultaneously.

• For details on an event/action, see the separate

manual (IMDP10001-61E).

SO

Sets the computational expression.

Mode

Operation mode

Setting

SOp1, p2, p3, p4, p5, p6

p1

Channel for computation:
Stand-alone model: A01 to A30
Expandable model: A01 to A60

p2

Computation on/off (on/off)

p3

Computational expression
(up to 40 characters)

p4

Span left value (-9999999 to 99999999)

p5

Span right value (-9999999 to 99999999)

p6

Position of decimal point for span (0 to 4)

Example

Set the sum of channel numbers 001 and 002 to
channel A01 for computation. Set -10.0000 to
15.0000 for the span.

SOA01, ON, 001+002, -100000, 150000, 4

Comments

• This command only works with the optional

computation function or if a pulse module is
installed.

• For details on operators, see the Appendix at

the end of this manual.

• If you wish to omit either p4, p5, or p6, omit

them all together.

• If pulse modules are installed and there is no

computation function, TLOG.PSOM will be the
only valid operator.

SK

Sets the computational constants.

Mode

Operation mode

Setting

SKp1, p2

p1

Computational constant number:
Stand-alone model : K01 to K30
Expandable model : K01 to K60

p2

Constants

Example

Set 300 to a computational constant K10.

SKK10, 300

Comments

• This command is effective only with the

optional computation functions.

• Constant setting ranges are -1.0000E35 to

-1.0000E-35, 0, 1.0000E-35 to 1.0000E35.