From the ―Communication Setting‖ screen,

Select ―Modbus Client Setting 3‖…..

This page is where Modbus addresses are

mapped into Communication Channels for

Reads/Writes to other devices via a ―Command
List‖. For Command ―No. 1‖, select ―Read‖…..

Enter ―1‖ for Server, ―255‖ for Unit, ―18001‖ for
Register. Then Select ―Bit String‖ under ―Data
Type‖. Enter ―C001

for the ―First Channel‖ and

―C005‖ for the ―last Channel‖. Modbus

addresses 18001 thru 18005 are now mapped

to Communication Channels 1 thru 5 which will

now reflect the Status data contained in Modbus

addresses 18001 thru 18005…..

Select ‖Apply‖ when settings

are complete…..