beautypg.com

Yokogawa Standalone MW100 User Manual

Page 10

background image

3. The ―RS Who‖ window will open showing current running drivers. In this example, there is an Ethernet driver

entitled ―AB_ETH

-1, Ethernet‖. Click on the ―+‖ symbol to the left of the driver. In the right window, connected

devices are shown.

4. Any devices connected to the ―AB_ETH

-1, Ethernet‖ driver now appear in the driver’s tree. In this example, there is a

Compact Logix processor located at IP address 192.168.1.95. For the DX Advanced or MW100 to be used as an

EtherNet IP device communicating to a Rockwell processor, the DX Advanced or MW100 must be mapped to an Ethernet

driver in RSLinx. An existing driver such as the ―AB_ETH-1, Ethernet‖ below may be used or a new driver created. For

this example, we are going to create a new driver in the next step.

7