The MSG Read instruction on Rung 0002 is configured as follows:

Type – Peer-To-Peer (default value, cannot be changed)

Read/Write – Read

Target Device – 500CPU

Local/Remote – Local

Control Block – N7:14

In the ―This Controller‖ area, enter the starting data

table address for the data to be received (F8:0), the Size in Elements

(number of data words) (10), and the Channel (0). In the ―Target Device‖ area, enter the starting data table address of the

MW100 (F10:0 for Measurement Channel 1). Enter the Local Node Address (45 – DF1 equivalent to 192.168.001.096 in

the ENI configuration. The ―Octal‖ section will fill in automatically).

Then click on the close window (X) at the top right of the Setup Screen (the screen can also be closed by clicking on the

―Setup Screen‖ In the MSG instruction. The MSG Write to the MW100 is now complete.