5.2 MicroLogix 1100
In this example, the system consists of a 1763 MicroLogix 1100, Series A processor and a 1762-IT4 Thermocouple Input
Module residing in the first expansion slot. The MicroLogix 1100’s IP address is 192.168.1.96. The MW100’s IP address is
192.168.001.101. The 1762-IT4 module’s four input channels are sent to the MW100’s Communication Channels C01
thru C04. The 1762-IT4’s channels are configured for ―Engineering Units‖ which will result in an integer value with an
implied decimal point (i.e. 66.8 = 668). The MW100’s Measurement Channels 001 thru 010 are being read and stored in
10 words starting with F8:0.
Data File ―MG10‖ has been created for Message Files. ―Data File RI11 has been created for storing Message Routing
Information.
Configuration of Channel 1
On the Project Tree, under the ―Controller‖ folder, double
-click on ―Channel Configuration‖ (or right click and select
―Open‖).
When the ―Channel Configuration‖ dialog box opens, click on the ―Channel 1‖ tab.