Yokogawa Standalone MW100 User Manual
Page 32
The MSG Read instruction is configured to use MSG File MG10:1
The MSG File Word Enable Bit (MG10:1/EN) is used to continuously toggle the instruction. If another data transmission
interval is required, configure the rung appropriately. Double clicking on the ―Setup Screen‖ portion of the instruction
accesses the MSG Instruction configuration.
In the ―This Controller‖ area, select the ―Channel‖ (1(Integral)), select the ―Communication Command‖ (500CPU Read),
the starting data table address for the data to be received (F:8.0), and the Size in Elements (number of data words) (10).
In the ―Target Device‖ area, enter the starting data table address of the MW100 (F10:0 for Measurement Channel #1), and
the ―Routing Information File (RI) (RI11:1). Then click on the ―MultiHop tab at the top of the Setup Screen.
In the ―To Address‖ area, enter the IP address of the MW100 (192.168.1.101). Then click on the close window (X) at the
top right of the Setup Screen (the screen can also be closed by clicking on the ―Setup Screen‖ In the MSG instruction.
The
MSG Read from the MW100 is now complete.
29