The Write Message is configured as shown below……
Message Type – CIP Data Table Write
Source Element – Tag - Local1:I.Ch0Data (1769-IT6 Channel 0)
Number of Elements – 6
Destination Element – int[3000] (DX Advanced Communication Channel C01)
The Message Write instruction on Rung 0 is configured as follows……
Click on the Message instruction ―View Configuration Dialog‖ button
In the ―Configuration area, select
the Message Type (CIP Data Table Write), select the Source Element tag
(Local:1:I.Ch0Data), enter the Number of Elements (6), and the Destination Element (int[3000], DX Advanced
Communication Channel C01). Then click on the ―Communication‖ tab.
Enter the ―Path‖ information. In this case the Ethernet port on the Compact Logix is used which would be
―LocalENB,2,192.168.001.100 (the ―2‖ is the communication depth on the Compact Logix). Select ―Connected‖ and
―Cache Connections‖ (speeds up communications). Click ―OK‖. The DX Advanced Write Message configuration is
complete.