3 setting for test output using hart communicator, Setting for test output using hart communicator -3 – Yokogawa ADMAG AXF User Manual
Page 85
IM 1E10C1-E
9-3
9. MAINTENANCE
9.1.3
Setting for Test Output Using HART Communicator
(1) Loop Test
This feature can be used to output a fixed current from 2.72 mA to 21.28 mA for loop
check.
Setting of Loop Test
1. Device setup
2. Diag/Service
2. Loop test
ADMAG SE :
WARN-Loop should be
removed from
automatic control
DEL
DEL
ABORT
OK
1
2
Set the control loop in manual mode, and press OK (F4).
Select “Other”, and press ENTER (F4).
1. 4mA:
Outputs a 4mA current signal
2. 20mA:
Outputs a 20mA current signal
3. Other:
Sets a desired output with the alphanumeric keys
4. End: Exits
Enter “12”, and press ENTER (F4).
Press OK (F4).
A fixed current of 12mA is output.
ADMAG SE :
Output
4.000
HELP
DEL
ABORT
ENTER
3
Call up “Loop test” display.
ADMAG SE :
Choose analog output
level
1 4mA
2 20mA
3 Other
4 End
DEL
DEL
ABORT
ENTER
ADMAG SE :
Fld dev output is
fixed at 12.000 mA
DEL
DEL
ABORT
OK
4
F4
(OK)
‘1 2’
×
2
Example: Set “12mA (50%)” as test output.
2. Loop test
F4
(ENTER)
F4
(OK)
F4
(ENTER)
1. In case “Bi direction” is set at “Output function”, the setting range is available
with –108 to +108%. Please set the loop test value in +/– percentage based on the
larger flow span within forward and reverse flow span.
2. In case “Auto 2 ranges” is set at “output function”, the loop test setting value
should be set in percentage based on the second range.
NOTE