2 setting flow span, Setting flow span -7, Example: flow span 30.0 m – Yokogawa ADMAG AXF User Manual
Page 45
IM 1E10C1-E
6-7
6. OPERATION VIA BRAIN TERMINAL
6.5.2
Setting Flow Span
Example: Flow span 30.0 m
3
/h
Select “B03:FLOW SPAN” using the arrow key and press ENTER
key to call up the following data setup panel.
Display
Description
Turn the power on and the panel as shown on the left appears after
“Please wait...” is displayed for a few seconds.
Pressing the ENTER key causes the initial data panel to be displayed.
Pressing the F4 key or ENTER key causes the menu panel to be
displayed.
Use the arrow key to select “B:SET” with the arrow key and press
the ENTER key.
Then, the parameter panel is displayed.
--WELCOME--
BRAIN TERMINAL
ID:BT200
CHECK CABLE CONNECTION
AND PRESS THE ENT KEY.
UTIL
FEED
ENTER
PARAM
B01:TAG NO
B02:DAMPING
3.0 s
B03:FLOW SPAN
1.00 m/s
DATA
DIAG
ESC
PARAM
01:MODEL
SE14-A00
02:TAG NO.
03:SELF CHECK
GOOD
OK
MENU
A:DISPLAY
B:SET
C:ADJUST
D:DISP SEL
E:TOTAL SET
F:PULSE SET
ENTER
ENTER
HOME
SET
ADJ
ESC
F4
or
ON/OFF
ENTER
SET
B03:FLOW SPAN
1.0000 m/s
0
DEL
CLR
ESC
“30.0”
Press ENTER key on the parameter panel to display the data setup
panel as shown on the left.
(If the security panel appears, enter the security code.*)
Enter “30.0” using the alphanumeric keys. Default:1.0000(m/s)
(This “B03: FLOW SPAN” is for entering the value, not units.)
* For entry of the security code, see IM1C0A11-01E.