7. OPERATION VIA HART COMMUNICATOR
(8) Multidrop Mode
Field devices in multidrop mode refer to the connection of several field devices on a
communication single line. Up to 15 field devices can be connected when set in the
multidrop mode. To activate multidrop communication, the field device address must be
changed to a number from 1 to 15. This change deactivates the 4 to 20 mA output and
turns it 4 mA. Refer to Fig. 7.1.2 for the load resistance.
Setting of Multidrop Mode
1. Device setup
4. Detailed setup
4. Outputs
3. HART output
1. Poll addr
ADMAG SE :
Poll addr
0
0
HELP
DEL
ESC
ENTER
Set the polling address (a number from 1 to 15) and press
ENTER (F4).
Then, press SEND (F2) to send the data.
Call up “Poll addr” display.
HART output
Online Menu
Main Menu
4. Utility
1. Configure Communication
1. Polling
ADMAG SE :
HART output
1 Poll addr 1
2 Num req preams 5
3 Burst mode On
4 Burst option PV
HELP
SAVE
HOME
ENTER
1
2
Return to “Online Menu” with HOME (F3).
Return to “Main Menu” with a “previous” key.
Select “Utility”.
Select “Configure Communication”.
Select “Polling”.
F3
(HOME)
Call up “Auto Poll” display.
ADMAG SE :
Online
1 Device setup
2 PV 20Cum/h
3 PV AO 20mA
4 Span 20Cum/h
HELP
SAVE
HOME
ENTER
F4
(ENTER)
‘1’
F2
(SEND)
3
JLK
4
HART Communicator
1 Offline
2 Online
3 Frequency Device
4 Utility
HELP
SEND
HOME
ENTER
4
HART Communicator
Utility
1 Configure Communic
2 system Information
3 Listen for PC
4 Storage Location
5 Simulation
HELP
SEND
HOME
ENTER
5
HART Communicator
Configure Communicat
1 Polling
2 Contrast
3 Off Time
4 Ignore diagnostics
HELP
SEND
HOME
ENTER