7. OPERATION VIA HART COMMUNICATOR
ADMAG SE :
Settting fld dev
output to 20mA
HELP
SAVE
ABORT
OK
11
12
Press OK (F4). The output signal of 100% is output.
Voltmeter reading: 5.210
Enter the reading of the voltmeter (5.210), and press ENTER
(F4).
Voltmeter reading: 5.000
Select “Yes” and press ENTER (F4).
“Returning fld dev to original output” appears.
Press OK (F4).
ADMAG SE :
Scaled output: 5.210
equal readout
device?
1 Yes
2 No
HELP
DEL
ABORT
ENTER
13
ADMAG SE :
Enter meter value
5.000000
5.000000
HELP
DEL
ABORT
ENTER
ADMAG SE :
NOTE-Loop may be
returned to automatic
control
DEL
DEL
ABORT
OK
14
‘5.21’
F4
(ENTER)
F4
(ENTER)
F4
(OK)
F4
(OK)
D/A trim should be executed only at single range mode. If D/A trim is executed at Bi
direction mode, it is feared that the current output becomes 108%.
IMPORTANT
- EJA120A (79 pages)
- EJA130A (2 pages)
- EJA130A (4 pages)
- EJA120A (31 pages)
- EJA130A (47 pages)
- EJA120A (40 pages)
- EJA438 (5 pages)
- EJA120A (6 pages)
- EJA115 (85 pages)
- EJA120A (47 pages)
- EJA210A (70 pages)
- EJA130A (4 pages)
- EJA430A (78 pages)
- EJA210E (89 pages)
- EJA210E (170 pages)
- EJX120A (4 pages)
- EJA210E (9 pages)
- EJX115A (55 pages)
- EJA210E (41 pages)
- EJA210E (96 pages)
- EJA210E (52 pages)
- EJX910A (9 pages)
- EJX910A (103 pages)
- FlowNavigator Software (163 pages)
- EJX910A (55 pages)
- EJX910A (175 pages)
- EJX910A (83 pages)
- EJA530A (67 pages)
- EJA120A (83 pages)
- EJX530A (52 pages)
- EJA110E (85 pages)
- EJA110E (4 pages)
- EJX120A (85 pages)
- EJA118 (76 pages)
- EJX118A (64 pages)
- EJA438 (72 pages)
- EJA430E (85 pages)
- EJX430A (40 pages)
- EJX430A (76 pages)
- EJA430E (7 pages)
- EJX430A (6 pages)
- EJA430E (41 pages)
- EJA430E (96 pages)
- EJX438A (10 pages)
- ADMAG AXR (194 pages)