IM 1E10C1-E
5-16
5. FUNCTION AND DATA SETTINGS
5.5.11 Totalization Switch Output
• In case the Internal Totalization Value increase over set level, an alarm signal is
output.
PLS/ALM+, PLS/ALM– terminals are for common use with pulse, alarm and other
status output functions. Therefore, in case this function is used, other functions are not
available to use.
Totalization switch can be selected as “05” in parameter
No. “b10”.
Switch level can be selected by calling up parameter No.
“E06”.
When using reversed status (ON/OFF) is required,
it can be set in
“N02 Output Mode”.
Display
Description
Code
00
01
02
03
04
05
Pulse output
Alarm output
Forward / reverse flow measurement
Automatic two range switching
Alarm output at low flow limit
Totalization switch
Content
Totalization
999999
Setting value
10000
Status
Output
ON
Input
Default : 00
Default : 0
NOTE
- EJA130A (47 pages)
- EJA120A (40 pages)
- EJA438 (5 pages)
- EJA120A (6 pages)
- EJA115 (85 pages)
- EJA120A (47 pages)
- EJA120A (79 pages)
- EJA130A (2 pages)
- EJA130A (4 pages)
- EJA120A (31 pages)
- EJA210A (70 pages)
- EJA130A (4 pages)
- EJA430A (78 pages)
- EJX115A (55 pages)
- EJA210E (41 pages)
- EJA210E (96 pages)
- EJA210E (52 pages)
- EJA210E (89 pages)
- EJA210E (170 pages)
- EJX120A (4 pages)
- EJA210E (9 pages)
- EJX910A (175 pages)
- EJX910A (83 pages)
- EJX910A (9 pages)
- EJX910A (103 pages)
- FlowNavigator Software (163 pages)
- EJX910A (55 pages)
- EJA530A (67 pages)
- EJA120A (83 pages)
- EJX530A (52 pages)
- EJA110E (4 pages)
- EJA110E (85 pages)
- EJX120A (85 pages)
- EJA118 (76 pages)
- EJX118A (64 pages)
- EJA438 (72 pages)
- EJA430E (85 pages)
- EJX430A (6 pages)
- EJX430A (40 pages)
- EJX430A (76 pages)
- EJA430E (7 pages)
- EJA430E (41 pages)
- EJA430E (96 pages)
- EJX438A (10 pages)
- ADMAG AXR (194 pages)