Wa t l o w S e r i e s S D 6 P I D w i t h D e v i c e N e t

6

Table 10. DeviceNet Object Class Attributes

Table 11. DeviceNet Object Instance Attributes

Table 13. Assembly Object Instance Attributes

Instance #

Access Rule

Name

DeviceNet Data
Type

Description of
Instance

Semantics of
Values

100

Get/Set

Poll Output

LONG + USINT

Poll Output

See Poll output in
section 6.2.4

101

Get

Poll Input

USINT + LONG +
USINT + USINT

Poll Input

See Poll input in
section 6.2.4

Attribute #

Access Rule

Name

DeviceNet Data
Type

Description of
Instance

Semantics of
Values

3

Get/Set

Data

Array of BYTES

See description
below

See description
below

Class Services: GET ATTRIBUTE SINGLE

Instance Services: *SET ATTRIBUTE SINGLE (when
MACID or BAUD RATE in PRG MODE), GET
ATTRIBUTE SINGLE, ALLOCATE M/S CONNECTION
SET, RELEASE M/S CONNECTION SET.

Assembly Object – “Static”

Class Code: 04hex

The Assembly Object binds attributes of multiple objects,
which allows data to or from each object to be sent or
received over a single connection. Assembly objects can be
used to bind input data or output data. The terms “input”
and “output” are defined from the network’s point of view.

An input will produce data on the network and an output
will consume data from the network.

The term “Static” implies: assemblies with member lists
defined by the device profile or by the manufacturer of the
product. The Instance number, number of Members, and
member list are fixed.

Table 12. Assembly Object Revision History

Revision

Description

01

Initial Release

02

Class-specific Service Code 4B
and 4C obsolete

Attribute #

Access Rule

Name

DeviceNet Data
Type

Description of
Attribute

Semantics of
Values

1

Get/Set*

MACID

USINT

Node Address

Range 0.. 63

2

Get/Set*

Baud Rate

USINT

Baud Rate

Range 0.. 2

4

Get

Bus-Off Counter

USINT

Number of times CAN
went to the bus-off
state

Range 0.. 255

5

Get

Allocation Information

Allocation Choice
Byte

Master’s MAC ID

STRUCT of:

BYTE

USINT

See Vol. I,

Section 5-5.4.2.

MAC ID of Master

(from Allocate)

Range 0.. 63, 255

Modified via Allocate
only

Attribute #

Access
Rule

Name

DeviceNet Data
Type

Description of
Attribute

Semantics of Values

1

Get

Revision

UINT

Revision of this object

The revision level of this
object. This is now at 2.