beautypg.com

Programmable object, Table 32. programmable class attributes, Table 31. programmable object revision history – Watlow Series SD6 PID Controller with DeviceNet Addendum User Manual

Page 26

background image

Wa t l o w S e r i e s S D 6 P I D w i t h D e v i c e N e t

2 6

Table 32. Programmable Class Attributes

Attribute #

Access
Rule

Name

DeviceNet
Data Type

Description of Attribute

Semantics of Values

1

Get

Revision

UINT

Revision of this object

The revision level of this
object (currently 1)

2

Get

Max Instance

UINT

Max allowed Instances of this
object

Always 1 for this Class

Class Services:

0x0E

GET ATTRIBUTE SINGLE

Instance Services:

0x0E

GET ATTRIBUTE SINGLE

0x10

SET ATTRIBUTE SINGLE

NOTE: All successful Explicit Message
Responses from a SET service will contain no
data. The response will be a two-byte message
containing the requester’s MAC ID and Service
Code (with R/R bit set).

Programmable Object

Class Code: 68hex

Programmable Object

The Programmable Object determines what parameters
appear on the Operations Page.

Table 31. Programmable Object Revision History

Revision

Description

01

Initial Release

Attribute #

Access
Rule

Name

DeviceNet
Data Type

Description of Attribute

Semantics of Values

134

Get/Set

Non volatile Write

BOOLEAN

Write to non volatile memory

(0) No

(1) Yes (default)

134

Get

Constant

UINT

Date Code

135

Get

Output 2 Process Value

UINT

Monitors Process Output 2
value via DeviceNet

00.00 to 22.00 units

136

Get/Set

Restore User Profile
Settings

BOOLEAN

Restores the customer-config-
ured settings.

(0) NO (default)

(1) YES

137

Get/Set

Save User Profile Settings

BOOLEAN

Saves the current customer-
configured settings.

(0) NO (default)

(1) YES