beautypg.com

Profile program object, Table 37. profile program object revision history – Watlow Series SD6 PID Controller with DeviceNet Addendum User Manual

Page 30

background image

Wa t l o w S e r i e s S D 6 P I D w i t h D e v i c e N e t

3 0

Class Services:

0x0E

GET ATTRIBUTE SINGLE

Instance Services:

0x0E

GET ATTRIBUTE SINGLE

0x10

SET ATTRIBUTE SINGLE

NOTE: All successful Explicit Message
Responses from a SET service will contain no
data. The response will be a two-byte message
containing the requester’s MAC ID and Service
Code (with R/R bit set).

Profile Program Object

Class Code: 6Ahex

Profile Program Object

The Profile Program Object provides access to parameters
that contain profile programs.

Table 37. Profile Program Object Revision History

Revision

Description

01

Initial Release

Attribute #

Access Rule

Name

DeviceNet
Data Type

Description of Attribute

Semantics of Values

113

Get

Hours Remaining

UINT

Indicates number of hours
remaining in the step cur-
rently running

0 to 99

114

Get

Minutes Remaining

UINT

Indicates number of minutes
remaining in the step cur-
rently running

0 to 59

115

Get

Seconds Remaining

UINT

Indicates number of seconds
remaining in the step cur-
rently running

0 to 59

116

Get

Ramp Rate

UDINT

Rate at which the profile
changes in degrees or units
per minute

0.0 to 9999.9 (*1000)

117

Get

Event Output 1 sta-
tus

BOOLEAN

Indicates Event Output 1 sta-
tus

(0)- OFF
(1)- ON

118

Get

Event Output 2 sta-
tus

BOOLEAN

Indicates Event Output 2 sta-
tus

(0)- OFF
(1)- ON

119

Get

Wait-for Process
Value

DINT

Profile clock waits until the
process value matches the
Wait-for value and continues
with the step

(Splo) to (sphi)

120

Get

Elapsed Jump
Count

UDINT

Number of times the profile
has been through the Jump
Loop Step

0 to 9999 (*1000)

121

Get

Failed File Number

UINT

Indicates the file number that
failed the Pre-Run check

1 to 4

122

Get

Failed Step Number

UINT

Indicates the step number
that failed the Pre-Run check

1 to 10

123

Get/Set

Comms
Temperature Units

BOOLEAN

This register determines the
units of measure for temper-
ature values during
DeviceNet communication

(0)- Fahrenheit (default)
(1)- Celsius