Profile program object, Table 37. profile program object revision history – Watlow Series SD6 PID Controller with DeviceNet Addendum User Manual
Page 30

Wa t l o w S e r i e s S D 6 P I D w i t h D e v i c e N e t
■
3 0
■
Class Services:
•
0x0E
GET ATTRIBUTE SINGLE
Instance Services:
•
0x0E
GET ATTRIBUTE SINGLE
•
0x10
SET ATTRIBUTE SINGLE
NOTE: All successful Explicit Message
Responses from a SET service will contain no
data. The response will be a two-byte message
containing the requester’s MAC ID and Service
Code (with R/R bit set).
Profile Program Object
Class Code: 6Ahex
Profile Program Object
The Profile Program Object provides access to parameters
that contain profile programs.
Table 37. Profile Program Object Revision History
Revision
Description
01
Initial Release
Attribute #
Access Rule
Name
DeviceNet
Data Type
Description of Attribute
Semantics of Values
113
Get
Hours Remaining
UINT
Indicates number of hours
remaining in the step cur-
rently running
0 to 99
114
Get
Minutes Remaining
UINT
Indicates number of minutes
remaining in the step cur-
rently running
0 to 59
115
Get
Seconds Remaining
UINT
Indicates number of seconds
remaining in the step cur-
rently running
0 to 59
116
Get
Ramp Rate
UDINT
Rate at which the profile
changes in degrees or units
per minute
0.0 to 9999.9 (*1000)
117
Get
Event Output 1 sta-
tus
BOOLEAN
Indicates Event Output 1 sta-
tus
(0)- OFF
(1)- ON
118
Get
Event Output 2 sta-
tus
BOOLEAN
Indicates Event Output 2 sta-
tus
(0)- OFF
(1)- ON
119
Get
Wait-for Process
Value
DINT
Profile clock waits until the
process value matches the
Wait-for value and continues
with the step
(Splo) to (sphi)
120
Get
Elapsed Jump
Count
UDINT
Number of times the profile
has been through the Jump
Loop Step
0 to 9999 (*1000)
121
Get
Failed File Number
UINT
Indicates the file number that
failed the Pre-Run check
1 to 4
122
Get
Failed Step Number
UINT
Indicates the step number
that failed the Pre-Run check
1 to 10
123
Get/Set
Comms
Temperature Units
BOOLEAN
This register determines the
units of measure for temper-
ature values during
DeviceNet communication
(0)- Fahrenheit (default)
(1)- Celsius