beautypg.com

Watlow Series SD6 PID Controller with DeviceNet Addendum User Manual

Page 19

background image

Wa t l o w S e r i e s S D 6 P I D w i t h D e v i c e N e t

1 9

Attribute #

Access
Rule

Name

DeviceNet
Data Type

Description of Attribute

Semantics of Values

170

Get/Set

Process Scale High mV

UDINT

Set the high scale for
process input

0.00 to 50.00 mV
(*1000) (when Sensor
Type set to mV, default =
50.00 mV)

171

Get/Set

Process Input Low error
mA

INT

Sets the low process value
that will cause an error to
occur for the process input

-1.00 to 10.00 mA (*100)
(Default = -1.00 mA)

172

Get/Set

Process Input Low error
Volts

INT

Sets the low process value
that will cause an error to
occur for the process input

-1.00 to 5.00 V
(*100)(Default = -1.00 V)

173

Get/Set

Process Input Low error
mV

INT

Sets the low process value
that will cause an error to
occur for the process input

-1.00 to 25.00 mV (*100)
(Default = -1.00 mV)

174

Get/Set

Process Input High error
mA

UINT

Sets the high process value
that will cause an error to
occur for the process input

10.00 to 21.00 mA
(*100) (Default = 21.00
mA)

175

Get/Set

Process Input High error
Volts

UINT

Sets the high process value
that will cause an error to
occur for the process input

5.00 to 11.00 V (*100)

(Default = 11.00V)

176

Get/Set

Process Input High error
mV

UINT

Sets the high process value
that will cause an error to
occur for the process input

25.00 to 51.00 mV
(*100) (Default =
51.00mV)

177

Get/Set

Output 1 Retransmit
Source

BOOLEAN

Set the control variable that
the retransmit signal repre-
sents

(0) - Process (default)

(1) - Set Point

178

Get/Set

Output 1 Retransmit Low
Scale

DINT

Set the low scale for the
retransmit output

-1999.0 to 9999.0
(*1000) (Default = 0)

179

Get/Set

Output 1 Retransmit
High Scale

DINT

Set the high scale for the
retransmit output

-1999.0 to 9999.0
(*1000) (Default = 500)

180

Get/Set

Output 1 Retransmit
Offset

DINT

Set the high scale for the
process output

-999.0 to 999.0 (*1000)
(Default = 0)

181

Get/Set

RTD Linearization

USINT

RTD type

(0) DIN (default)

(1) Unused 1

(2) Unused 2