Watlow Series SD6 PID Controller with DeviceNet Addendum User Manual
Page 23

Wa t l o w S e r i e s S D 6 P I D w i t h D e v i c e N e t
■
2 3
■
Attribute #
Access
Rule
Name
DeviceNet
Data Type
Description of Attribute
Semantics of Values
122
Get
Integral Term
UINT
View the active integral term
for PID diagnostics.
0.000 to 1.000
(this value multiplied by
100 equals the percent
power)
123
Get
Derivative Term
UINT
View the active derivative term
for PID diagnostics.
0.000 to 1.000
(this value multiplied by
100 equals the percent
power)
124
Get/Set
Alarm 1 High Temperature
DINT
Set the high alarm set point.
0 to 9999 (* 1000) if
Sensor Type is set to
Thermocouple or RTD
(default = 999)
125
Get/Set
Alarm 1 High Process
DINT
Set the high alarm set point.
-1999 to 9999 (* 1000) if
Sensor Type is set to mA
or Volt.
(default = 1500)
126
Get/Set
Alarm 1 Low Temperature
DINT
Set the low alarm set point.
-1999 to 0 (* 1000) if
Sensor Type is set to
Thermocouple or RTD
(default = -999)
127
Get/Set
Alarm 1 Low Process
DINT
Set the low alarm set point.
-1999 to 9999 (* 1000) if
Sensor Type is set to mA
or Volt.
(default = 32)
128
Get/Set
Alarm 2 High Temperature
DINT
Set the high alarm set point.
0 to 9999 (* 1000) if
Sensor Type is set to
Thermocouple or RTD
(default = 999)
129
Get/Set
Alarm 2 High Process
DINT
Set the high alarm set point.
-1999 to 9999 (* 1000) if
Sensor Type is set to mA
or Volt.
(default = 1500)