Wa t l o w S e r i e s S D 6 P I D w i t h D e v i c e N e t

2 3

Attribute #

Access
Rule

Name

DeviceNet
Data Type

Description of Attribute

Semantics of Values

122

Get

Integral Term

UINT

View the active integral term
for PID diagnostics.

0.000 to 1.000

(this value multiplied by
100 equals the percent
power)

123

Get

Derivative Term

UINT

View the active derivative term
for PID diagnostics.

0.000 to 1.000

(this value multiplied by
100 equals the percent
power)

124

Get/Set

Alarm 1 High Temperature

DINT

Set the high alarm set point.

0 to 9999 (* 1000) if
Sensor Type is set to
Thermocouple or RTD

(default = 999)

125

Get/Set

Alarm 1 High Process

DINT

Set the high alarm set point.

-1999 to 9999 (* 1000) if
Sensor Type is set to mA
or Volt.

(default = 1500)

126

Get/Set

Alarm 1 Low Temperature

DINT

Set the low alarm set point.

-1999 to 0 (* 1000) if
Sensor Type is set to
Thermocouple or RTD

(default = -999)

127

Get/Set

Alarm 1 Low Process

DINT

Set the low alarm set point.

-1999 to 9999 (* 1000) if
Sensor Type is set to mA
or Volt.

(default = 32)

128

Get/Set

Alarm 2 High Temperature

DINT

Set the high alarm set point.

0 to 9999 (* 1000) if
Sensor Type is set to
Thermocouple or RTD

(default = 999)

129

Get/Set

Alarm 2 High Process

DINT

Set the high alarm set point.

-1999 to 9999 (* 1000) if
Sensor Type is set to mA
or Volt.

(default = 1500)