beautypg.com

Watlow Series SD6 PID Controller with DeviceNet Addendum User Manual

Page 25

background image

Wa t l o w S e r i e s S D 6 P I D w i t h D e v i c e N e t

2 5

Table 30. Factory/Calibration Object Instance Attributes

Attribute #

Access
Rule

Name

DeviceNet
Data Type

Description of Attribute

Semantics of Values

100

Get

Ambient Temperature

DINT

Displays the current calculat-
ed ambient temperature.

-50.0 to 300.0°F

(* 1000)

101

Get

Output 1 Process Value

UINT

Monitors Process Output 1
value via DeviceNet

00.00 to 22.00 units

102

Get/Set

Restore Factory
Calibration

BOOLEAN

Replaces the user calibration
parameters with the factory
calibration parameters.

(0) NO (default)

(1) YES

103

Get/Set

Restore User Settings

BOOLEAN

Restores the customer-config-
ured settings.

(0) NO (default)

(1) YES

104

Get/Set

Save User Settings

BOOLEAN

Saves the current customer-
configured settings.

(0) NO (default)

(1) YES

105

Get/Set

Default Parameters

BOOLEAN

Reset all parameters to their
default values.

(0) NO (default)

(1) YES

106

Get

Output 1 Type

USINT

Displays the hardware type for
Output 1.

(0) None

(1) DC/Open Col.

(2) Mech. Relay

(3) S.S. Relay

(4) Process

107

Get

Output 2 Type

USINT

Displays the hardware type for
Output 2.

(0) None

(1) DC/Open Col.

(2) Mech. Relay

(3) S.S. Relay

(4) Process

108

Get

Software ID

UINT

Software ID number

0 to 9999

109

Get

Software Build Number

UINT

Software built number

0 to 9999 Build Number

110

Get

Serial Number

UDINT

Serial number

0 to 99999999